Emerson 5300 TV Converter Box User Manual


 
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-28
Table 1-16. Output Variables for
Floating Point Format Code 3
Slave 1 SV 2104
Secondary variable from slave 1
represented in IEEE 754 format, using
Floating Point Format Code 2.
Slave 1 TV 2106
Tertiary variable from slave 1
represented in IEEE 754 format, using
Floating Point Format Code 2.
Slave 1 FV (QV) 2108
Fourth variable from slave 1 represented
in IEEE 754 format, using Floating Point
Format Code 2.
Register Name Register Number Note
Register Name Register Number Note
Slave 1 Status 2200
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV.
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or
other master present)
Bit 15: HTM Task not running (option not
available).
Note: Bit 1-3 is set when Invalid
Measurement of Slave 1 Non PV, i.e. all
three bits are set simultaneously.
Slave 1 PV 2202
Primary variable from slave 1
represented in IEEE 754 format, using
Floating Point Format Code 3.
Slave 1 SV 2204
Secondary variable from slave 1
represented in IEEE 754 format, using
Floating Point Format Code 3.
Slave 1 TV 2206
Tertiary variable from slave 1
represented in IEEE 754 format, using
Floating Point Format Code 3.
Slave 1 FV (QV) 2208
Fourth variable from slave 1 represented
in IEEE 754 format, using Floating Point
Format Code 3.