TROUBLESHOOTING No communication on RS-485 bus (MA, MB)
Check that the cables are connected
Check that PWR+ is connected to + and PWR- is connected to - on the
power supply
Make sure the 5300/5400 transmitter is supplied with 8-30 Vdc
(max. rating)
Try alternating MA/MB if you are unsure of the polarity
If an RS-485 converter is used, make sure it is properly installed and
configured
The last 5300/5400 transmitter may need a terminating 120-resistor
connected between MA and MB
No 5300/5400 communication in RRM
Using HART+, HART-
• HART modem is not properly connected
• Polling address is incorrect in RRM (default 1)
Using MA, MB
• See No communication on RS-485 bus
• Polling address is incorrect in RRM (default 1)
• Cycle the power and wait 20 seconds before polling
No communication with Modbus RTU protocol
•See No communication on RS-485 bus
Make sure the “Modbus Communication Protocol Configuration” is
done properly
Make sure the Modbus RTU address is unique on the bus
Cycle the power and try to connect
Check the RTU communication settings
No communication with Modbus ASCII protocol
•See No communication on RS-485 bus
Make sure the “Modbus Communication Protocol Configuration” is
done properly
Make sure the Modbus ASCII address is unique on the bus
Cycle the power, waiting 40 seconds before communication begins
Check the RTU communication settings
No communication with Levelmaster protocol
•See No communication on RS-485 bus
Make sure the “Modbus Communication Protocol Configuration” is
done properly
Make sure the Levelmaster address is unique on the bus
Cycle the power, waiting 40 seconds before communication begins
Check the RTU communication settings