MODEL TCL SECTION 7
SOFTWARE CONFIGURATION
7.7 CHANGING ALARM PARAMETERS
3. Press any key to enter the main menu. Move the cursor to "Program"
and press Enter (F4).
4. Move the cursor to "Configure" and press Enter (F4).
5. Move the cursor to "Alarms" and press Enter (F4).
6. Nine menu headers relate to alarms. Alarms 1, 2 and 3, each have a
control header and a setup header. Alarm 4 has only a setup header.
The eighth menu header is for configuring the feed limit timer, and the
ninth menu header is for configuring the interval timer.
Always configure the control parameters BEFORE making
changes in the alarm setup.
To access a header, move the cursor to the desired header and press
Enter (F4).
7. Alarm Control Settings:
a. Move the cursor to the desired output control header. Press Enter
(F4).
b. With the cursor on "Activation method" press Enter (F4).
Alarm 1 control
Alarm 1 setup
Alarm 2 control
Exit Enter
Outputs
Alarms
pH
Exit Enter
Output setpoints
Simulated tests
Configure
Exit Enter
1. This section describes how to configure the controller alarms. Alarms 1, 2, and 3 can be assigned to the main
measurement (total chlorine) or temperature. In addition, alarm 1, 2, or 3 can be configured as a feed limit
timer or as an interval timer (see steps 10 and 11). Alarm 4 is always a fault alarm.
2. An alarm assigned to the main measurement or temperature can be configured as either a simple on/off alarm
or as TPC (time proportional control) alarm.
Activation method
Control mode
Exit Enter