Toshiba T2 Projection Television User Manual


 
6 F 3 B 0 3 6 4
133
Table 6. 3 Combined Indications of the 7
-
Segment LED and 2
-
Color LED
M: DN211 node address S: Slave device node address
7
-
segment LED MS NS Description
78 S Green
lighting
Red
blinking
When unable to start communicating with one or more
slave devices in the scan list
79 M Green
lighting
Red
blinking
1) When the "START" bit was not set to "1" at run
request (followed by the indication of 78 S )
2) When response from all slaves ceased during
normal transmission (followed by the indication of 72
S )
3) No slave device is found in network when starting
transmission (this display only)
84 M Green
lighting
Green
blinking
When the slave devices were not initialized
91 M Green
lighting
Red
lighting
When busoff occurred (communication halt was
chosen when busoff occurred)
92 M Green
lighting
Not lit 1) No network power is supplied to the 1DN211.
2) The network connector on the DN211 was
disconnected.
A0 - CA Irregular Irregular When requests to the T2/T2E/T2N are completed
unsuccessfully, completion status (Table 4.17) is
indicated on the 7-segment LED.
F0 M Red
lighting
Not lit Down mode: Watchdog timeout error
F1 M Red
blinking
Not lit Down mode: Memory bus trouble occurred
F2 M Red
blinking
Not lit Down mode: TRAP occurred
F3 M Red
lighting
Not lit Down mode: BCC check error occurred on ROM
(at DN211 startup)
F4 M Red
lighting
Not lit Down mode: Read/write error occurred on RAM
(at DN211 startup)
F5 M Red
lighting
Not lit Down mode: Read/write error occurred on the
T2/T2E/T2N communication memory at
DN211 startup
F6 M Red
blinking
Not lit Down mode: DN211 node address setting abnormal
F7 M Red
blinking
Not lit Down mode: DN211 network communication rate
setting abnormal
F8 M Red
blinking
Not lit Down mode: EEPROM for scan list read error
occurred