1. Safety
1.3 Important warnings
Important warnings:
Risk of electric shock:
Do not open. To reduce the risk of electric shock, do not remove cover (or back). No user-serviceable parts inside. Refer servicing
to qualified service personnel.
RISK OF ELECTRICAL SHOCK
DO NOT OPEN
CAUTION
CAUTION : TO REDUCE THE RISK OF ELECTRIC SHOCK,
DO NOT REMOVE COVER (OR BACK)
NO USER-SERVICEABLE PARTS INSIDE
REFER SERVICING TO QUALIFIED SERVICE PERSONNEL
The lightning flash with an arrowhead within a triangle is intended to tell the user that p
arts inside this product may cause a risk of
electrical shock to persons.
The exclamation point within a triangle is intended to tell the user that important operating and/or servicing instructions are included
in the technical documentation for this equipment.
Maximum and minimum ambient temperature:
The maximum ambient temperature for the LED wall is 40 °C, the minimum temperature is 0 °C.
High leakage current:
The combination of multiple tiles in an installation results in increased levels of leakage current. In order to avoid risk of electric
shock due to high leakage current, proper grounding of the installation is required.
Flammable materials:
Keep flammable materials away from the installation (such as curtains). A lot of energy is transferred into heat. The installation
should be such that the amount of air flow required for safe operation of the equipment is not compromised. Proper ventilation must
be provided.
ESD and LED’s:
LED components used in ILite display devices are ESD (Electro-Static Discharge) sensitive. To prevent the possibility of destroying
LED components do not touch either in operation or while switched off.
Risk of electric shock / Risk of fire: To protect against risk of fire caused by overloading of power cables, MAXIMUM six (6) tiles
may be connected in parallel. Each power source cable sup
plying maximum six (6) tiles should be protected by a circuit breaker
or fuses rated 16 A / 250 VAC (15 A / 250 VAC in the USA and Canada). Note that one ILite tile requires 200-240 VAC, 50-60 Hz,
1.45 amps at 230 VAC.
Disconnect device:
When the appliance inlets of the individual tiles a
re not accessible, the socket outlets supplying the rack shall be installed near the
equipment and be easily accessible, or a readily accessible general disconnect device shall be incorporated in the fixed wiring.
This equipment MUST be earthed:
In order to protectagainst risk of electric shock, the installation should be properly grounded. Defeating the purpose of the grounding
type plug will expose you to the risk of electric sh
ock.
Power system:
It is recommended to use a TN-S power distribution system (a power distribution system with a separate neutral and grounding
conductor) in order to avoid large ground current loops due to voltage differences in the neutral conductor. The total electrical
installation should be protected by an appr
opriately rated disconnect switch, circuit breakers and Ground Fault Current Interrupters.
The installation shall be done according to the local electrical installation codes. In Europe special attention should be given to EN
60364, the standard for electrical installation of buildings. In Germany VDE 0100 should be adhered to.
Mains cords:
The power cords delivered with this sys
tem have special properties for safety. They are not user serviceable. If the power cords are
damaged, replace them only with new ones. Never try to repair a power cord.
6
R5976522 FIXED ILITE DISPLAY 17/11/2006