04/08 UDC3200 Universal Digital Controller Operator Manual 27
Function
Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter Definition
RSET2MIN
RSET2RPM
0.02 to 50.00 These are the same as above except that they apply to Duplex
models for the "COOL" zone of Heat/Cool applications or for the
second set of PID constants.
CYC SEC
or
CYC SX3
1 to 120
CYCLE TIME (HEAT) determines the length of one time
proportional output relay cycle. Defined as "HEAT" cycle time for
Heat/Cool applications.
CYC SEC—Electromechanical relays
CYC SX3—Solid state relays
ATTENTION Cycle times are in either second or 1/3-second
increments depending upon the configuration of RLY TYPE in the
Output Algorithm Set Up group.
CYC2 SEC
or
CYC2 SX3
1 to 120
CYCLE TIME 2 (COOL) is the same as above except it applies to
Duplex models as the cycle time in the "COOL" zone of Heat/Cool
applications or for the second set of PID constants.
CYC2 SEC—Electromechanical relays
CYC2 SX3—Solid state relays
ATTENTION Cycle times are in either second or 1/3-second
increments depending upon the configuration of RLY TYPE in the
Output Algorithm Set Up group.
SECURITY
0 to 9999
SECURITY CODE—The level of keyboard lockout may be
changed in the Set Up mode. Knowledge of a security code may
be required to change from one level to another. This configuration
should be copied and kept in a secure location.
NOTE: The Security Code is for keyboard entry only and is not
available via communications.
ATTENTION Can only be changed if LOCKOUT selection is
NONE.
LOCKOUT
LOCKOUT applies to one of the functional groups: Configuration,
Calibration, Tuning, Accutune. DO NOT CONFIGURE UNTIL ALL
CONFIGURATION IS COMPLETE.
NONE
NONE—No lockout; all groups are read/write.
CALIB
CALIB—All groups are available for read/write except for the
Calibration and Keyboard Lockout groups.
+ CONF
+ CONF—Tuning, SP Ramp, and Accutune groups are read/write.
All other groups are read only. Calibration and Keyboard Lockout
groups are not available.
+ VIEW
+ VIEW—Tuning and Setpoint Ramp parameters are read/write.
No other parameters are viewable.
MAX
MAX—Tuning and Setpoint Ramp parameters are available for
read only. No other parameters are viewable.