Honeywell UDC3200 Universal Remote User Manual


 
04/08 UDC3200 Universal Digital Controller Operator Manual 45
3.9 Input 2 Set Up Group
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
IN2 TYPE
ATTENTION
Changing the input
type will result in the
loss of Field
Calibration values and
will restore Factory
Calibration values.
Selecting Position
Proportional Control in
the Output Setup
Group forces Input 2
to the Slidewire
Selection.
DISABLE
B TC
E TC H
E TC L
J TC H
J TC M
J TC L
K TC H
K TC M
K TC L
NNM H
NNM L
NIC H
NIC L
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
0-20mA
4-20mA
0-10mV
0-50mV
0-100mV
0-5 V
1-5 V
0-10 V
TC DIFF
SLIDEW
INPUT 2 ACTUATION TYPE – This selection
determines what actuation you are going to use for
Input 2.
DISABLE—Disables Input.
B TC—B Thermocouple
E TC H—E Thermocouple High
E TC L—E Thermocouple Low
J TC H—J Thermocouple High
J TC M—J Thermocouple Med
J TC L—J Thermocouple Low
K TC H—K Thermocouple High
K TC M—K Thermocouple Med
K TC L—K Thermocouple Low
NNM H—Ni-Ni-Moly Thermocouple High
NNM L—Ni-Ni-Moly Thermocouple Low
NIC H—Nicrosil-Nisil Thermocouple High
NIC L—Nicrosil-Nisil Thermocouple Low
R TC—R Thermocouple
S TC—S Thermocouple
T TC H—T Thermocouple High
T TC L—T Thermocouple Low
W TC H—W5W26 Thermocouple High
W TC L—W5W26 Thermocouple Low
100 PT—100 Ohm RTD High
100 LO—100 Ohm RTD Low
200 PT—200 Ohm RTD
500 PT—500 Ohm RTD
RAD RH—Radiamatic RH
RAD RI—Radiamatic RI
0-20mA—0 to 20 Milliamperes
4-20mA—4 to 20 Milliamperes
0-10mV—0 to 10 Millivolts
0-50mV—0 to 50 Millivolts
0-100mV—0 to 100 Millivolts
0-5 V—0 to 5 Volts
1-5 V—1 to 5 Volts
0-10 V—0 to 10 Volts
TC DIFF—Thermocouple Differential
SLIDEW—Slidewire (For Position Proportional
Applications)
XMITTER2
B TC
E TC H
E TC L
J TC H
J TC M
J TC L
K TC H
K TC M
K TC L
NNM H
NNM L
NIC H
NIC L
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
LINEAR
SQROOT
TRANSMITTER CHARACTERIZATION—This
selection lets you instruct the controller to
characterize a linear input to represent a non-linear
one.
ATTENTION Prompt only appears when a linear
actuation is selected at prompt IN2 TYPE.
Parameter definitions are the same as in IN2 TYPE.