04/08 UDC3200 Universal Digital Controller Operator Manual 63
3.14 Display Set Up Group
Function
Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter Definition
DECIMAL
DECIMAL POINT LOCATION—This selection determines where
the decimal point appears in the display.
NONE
ONE
TWO
THREE
NONE—No Decimal Place—fixed, no auto-ranging
ONE—One Place
TWO—Two Places
THREE—Three Places
ATTENTION Auto-ranging will occur for selections of one, two or
three decimal places. For example, should the instrument be
configured for two decimal places and the PV exceeds 99.99, then
the display will change to a single decimal place so that values of
100.0 and above can be shown.
TEMP UNIT
TEMPERATURE UNITS—This selection will affect the indication
and operation.
DEG F
DEG F—Degrees Fahrenheit – Degrees F Annunciator lighted
DEG C
DEG C—Degrees Centigrade – Degrees C Annunciator lighted
NONE
NONE—No temperature annunciators lighted. Upper and Lower
Displays will show temperature in Degrees Fahrenheit when inputs
are configured for Thermocouple or RTD types.
PWR FREQ
60 HZ
50 HZ
POWER LINE FREQUENCY—Select whether your controller is
operating at 50 or 60 Hertz.
ATTENTION For controllers powered by +24 Vdc, this
configuration should be set to the AC line frequency used to
produce the +24 Vdc supply.
Incorrect setting of this parameter may cause normal mode noise
problems in the input readings.
RATIO 2
INPUT 2 RATIO—This enables the Ratio for Input 2 to be set from
the front panel. Input 2 must be installed and enabled for this
configuration to operate.
DISABLE
DISABLE—Disables setting Ratio 2 from front panel.
ENABLE
ENABLE—Allows the Ratio for Input 2 to be set through the
keyboard.
LANGUAGE
ENGLISH
FRENCH
GERMAN
SPANISH
ITALIAN
LANGUAGE—This selection designates the prompt language.
ENGLISH
FRENCH
GERMAN
SPANISH
ITALIAN