Configuration Guide
A016-1CG-1.00-2 General
2
Full
1.1 Configuration Sequence
The following is a list of the steps required to configure the A016-1 C3000/C0300 DPA:
1. Edit the C3000/C0300 DPA configuration. Prepare it according to the guidelines in this
document and the specific use for which the C3000/C0300 DPA is required.
2. Edit the configuration for the other applications that will run on the product. Prepare them
according to their own configuration guides.
3. Generate the configuration and download it to the product using a Config Pro Configuration
System. The list of applications to be compiled must include the C3000/C0300 DPA,
application A016-1.
4. Restart the system. If the C3000/C0300 DPA encounters an error during its initialization, it
will log a message to the WESMAINT Error Log and then, depending on the severity of the
error, terminate or continue with its run-time function.
5. Check for error messages. Log into the WESMAINT maintenance interface, select the
System Functions item from the Main menu, and then select the Error Log item from the
System Functions menu. If any error messages are displayed, correct the problem as
described in Appendix A: Error Messages and repeat steps 3 through 5. When the
C3000/C0300 DPA has successfully validated all the configuration parameters, configuration
is complete.