GE Power Systems
Custom ABB C3000/C0300 DPA
Configuration Guide
A016-1CG-1.00-2 General
38
Full
ERR 2314: INVALID SOE GROUP METHOD REC <xx>
Why:
• The A016_GRP table has an invalid SOE group method. This may be caused by the
corruption of the configuration table.
• Remedy:
• Rebuild and re-download the configuration. If the problem persists contact customer service.
ERR 2400: INVALID SECTION TYPE, REC <xx>
Why:
• The Section Type entry for the indicated A016SCAN record number is not within the valid
entry range described earlier in this document.
Remedy:
• Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2401: INVALID TABLE OFFSET, REC <xx>
Why:
• The Section Offset entry for the indicated A016SCAN record number is not within the valid
entry range described earlier in this document.
Remedy:
• Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2500: INVALID POINT, REC <xx>
Why:
• The DI Point Number entry for the indicated A016_DI record number is not within the valid
entry range described earlier in this document.
Remedy:
• Modify and re-download the configuration with a correct entry in the specified configuration
record.