GE A016-1CG Cable Box User Manual


 
GE Power Systems
Custom ABB C3000/C0300 DPA
Configuration Guide
A016-1CG-1.00-2 General
42
Full
ERR 2801: INVALID TRIP DURATION, REC <xx>
Why:
The Trip Duration entry for the indicated A016_TC record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2802: INVALID CLOSE DURATION, REC <xx>
Why:
The Close Duration entry for the indicated A016_TC record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2803: INVALID OPERATION MODE, REC <xx>
Why:
The Operation Mode entry for the indicated A016_TC record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2900: INVALID RAISE POINT, REC <xx>
Why:
The Raise Point Number entry for the indicated A016_RL record number is not within the
valid entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.