Chapter 4: Configuring the C3000/C0300
DPA A016_LRU Table
This chapter describes entries the user must provide in the A016_LRU table found in the
C3000/C0300 DPA configuration.
The A016_LRU table provides information for LRUs, which are used by the C3000/C0300 DPA.
It contains one record for each LRU configured, for database customization. The fields contained
in the table are described in the following table:
Table 5 A016_LRU Table Fields
Field Range Description
Local/Remote
Input
Any valid system Digital
Input point or Undefined
(-1).
The system DI point number, which is used to switch the LRU between local
and remote operation. In local mode, LRU controls are disabled, and in
remote mode, LRU controls are enabled. The high entry limit is confined to
the highest status point number configured in the system. Entering Undefined
(-1) disables the local/remote option and the LRU is always in remote mode
(controls enabled).
Local/Remote
State
0 to 1 The state (0 or 1) of the local/remote input which corresponds to the local
(controls disabled) mode. This entry is ignored if the local/remote option is
disabled.
Accum. Freeze
Output
Any valid system Digital
Output point or
Undefined (-1).
The system control output point number (zero-based), which is to be pulsed
on when an accumulator freeze (update) command is received from the
master station. The high entry limit is confined to the highest control point
number configured in the system. Entering -1 disables the freeze output
option.
Accum Freeze
Time
1 to 60000 The time duration in milli-seconds that the freeze output relay is pulsed on.
This entry is ignored if the freeze output option is disabled.
T/C Select
Timeout
1 to 60 The amount of time in seconds that the C3000/C0300 DPA allows execution
of a trip or close request after enabling a control point selection.