GE A016-1CG Cable Box User Manual


 
GE Power Systems
Custom ABB C3000/C0300 DPA
Configuration Guide
A016-1CG-1.00-2 General
44
Full
ERR 2905: INVALID LOWER INC DURATION, REC <xx>
Why:
The Lower Inc. Duration entry for the indicated A016_RL record number is not within the
valid entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 3000: INVALID POINT NUMBER, REC <xx>
Why:
The Setpoint Number entry for the indicated A016_SP record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 3001: INVALID OPTIONS, REC <xx>
Why:
The Setpoint Options entry for the indicated A016_SP record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 3002: INVALID RANGE, REC <xx>
Why:
The Range entry for the indicated A016_SP record number is not within the valid entry range
described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.