Custom ABB C3000/C0300 DPA
Configuration Guide
A016-1CG-1.00-2 General
8
Full
Field Range Description
Number of SOEs 10 to 255 (When SOE
Methods is set to Time
Correlated)
10 to 2000 (When SOE
Methods is set to Time
Sync)
The maximum number of SOE events that can be buffered per group of points.
Group Offset Indexes into A016_GRP
table.
The one based offset from the first entry in the A016
_
GRP table. The
A016
_
GRP table is described in a later chapter.
Group Count 0 to 16 The number of A016_GRP records which correspond to this LRU. This entry
is used in conjunction with the LRU Group Offset entry to determine the
exact range of records in the A016
_
GRP table that this LRU is to utilize.
Possible entries accepted by the C3000/C0300 DPA are from 0 to 16, but the
entered value, plus the LRU Group Offset entry, must not exceed the number
of records in the A016_GRP table.
SOE Methods Time Correlated or Time
Sync
This entry sets the SOE reply method when the master station sends a SOE
data request or a Scan Data request.