GE A016-1CG Cable Box User Manual


 
Custom ABB C3000/C0300 DPA
Configuration Guide
GE Power Systems
General A016-1CG-1.00-2
Full
39
ERR 2501: INVALID OPTIONS, REC <xx>
Why:
The DI Point Options entry for the indicated A016_DI record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified
configuration record.
ERR 2600: INVALID POINT, REC <xx>
Why:
The AI Point Number entry for the indicated A016_AI record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2601: INVALID MODE, REC <xx>
Why:
The Conversion Mode entry for the indicated A016_AI record number is not within the
valid entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2602: INVALID RANGE, REC <xx>
Why:
The Range entry for the indicated A016_AI record number is not within the valid entry range
described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.