Configuration Guide
A016-1CG-1.00-2 General
32
Full
ERR 2101: INVALID OFFSET, REC <xx>
Why:
The LRU Offset entry for the indicated A016_XRF record number is not within the valid entry
range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2200: INVALID LOCAL/REMOTE POINT, REC <xx>
Why:
The Local/Remote entry for the indicated A016_LRU record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2201: INVALID LOCAL STATE, REC <xx>
Why:
The Local State entry for the indicated A016_LRU record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2202: INVALID FREEZE POINT, REC <xx>
Why:
The Freeze Output entry for the indicated A016_LRU record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.