Custom ABB C3000/C0300 DPA
Configuration Guide
A016-1CG-1.00-2 General
40
Full
ERR 2603: INVALID DIVISOR, REC <xx>
Why:
The Divisor entry for the indicated A016_AI record number is not within the valid entry
range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2604: INVALID OFFSET, REC <xx>
Why:
The Offset entry for the indicated A016_AI record number is not within the valid entry
range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2605: INVALID DEADBAND, REC <xx>
Why:
The Dead Band entry for the indicated A016_AI record number is not within the valid entry
range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.
ERR 2606: INVALID LIMIT, REC <xx>
Why:
The Alarm Limit entry for the indicated A016_AI record number is not within the valid
entry range described earlier in this document.
Remedy:
Modify and re-download the configuration with a correct entry in the specified configuration
record.