Chapter 11: Configuring the
C3000/C0300 DPA A016_RL Table
This chapter describes entries the user must provide in the A016_RL table found in the
C3000/C0300 DPA configuration.
The A016_RL table provides information for Raise/Lower control output points, which are used
by the C3000/C0300 DPA. The table contains one record for each Raise/Lower control output
point to customize the usage of the point. The fields contained in the table are described in the
following table:
Table 12 A016_RL Table Fields
Field Range Description
Raise DO Point
Any valid system Digital
Output point or Undefined (-1).
The system control output point number, which is used as the
destination for a Raise DO control point. The high entry limit is confined
to the highest system control output point configured in the system.
Entering Undefined (-1) disables Raising of the protocol point.
Raise Base
Duration
0 to 30000
This is the base duration, in milliseconds, used to operate for when a
Raise is requested for the protocol point corresponding to this record,
via the formula:
pulse duration = (inc. duration * mult.) + base duration
where the inc. duration is also configurable and the mult. factor is
specified in the master Raise/Lower request.
Raise Inc.
Duration
1 to 30000
This is the incremental duration, in milli-seconds, used to specify how
long the control output contact is to operate for when a Raise is
requested for the protocol point corresponding to this record, via the
formula:
pulse duration = (inc. duration * mult.) + base duration
where the base duration is also configurable and the mult. factor is
specified in the master Raise/Lower request.