GE A016-1CG Cable Box User Manual


 
GE Power Systems
Custom ABB C3000/C0300 DPA
Configuration Guide
A016-1CG-1.00-2 General
26
Full
A.1 Fatal Error Messages
ERR 1000: TERMINATING, PRIMARY CONFIG NOT FOUND
Why:
The application cannot find its primary configuration information table A016_COM.
Remedy:
Review the section in this document about configuring the A016_COM table and verify the
table has been correctly defined and loaded into memory. NOTE: The A016_COM table
may be deleted from memory in order to intentionally disable the application.
ERR 1001: NO A016_COM RECORDS FOUND
Why:
The application found an A016_COM configuration table in memory, but the table
contained no records.
Remedy:
Ensure that at least one record has been defined and loaded into memory for the A016_COM
table.
ERR 1002: NO A016_XRF RECORDS FOUND
Why:
The application could not find any A016_XRF configuration table records in memory.
Remedy:
Ensure that at least one record has been defined and loaded into memory for the A016_XRF
table.
ERR 1003: NO A016_LRU RECORDS FOUND
Why:
The application could not find any A016_LRU configuration table records in memory.
Remedy:
Ensure that at least one record has been defined and loaded into memory for the A016_LRU
table.