2 - 128
TAIAN PLC
49 TAIAN PLC
49
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Available Memory
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
PLC
TP02
RS-422 [Wiring Diagram 1]
RS-422 [Wiring Diagram 2]
Select PLC Type
TP02
Communication Port (T/R+, T/R-)
MMI Port (9pin) (4-5 Short Computer Link Mode)
PORT
Wiring Diagram
19200bps
1
None
None
1
Port
Baud Rate
Parity
Data Length
Stop Bit
Item Setting of PLC
19200bps
77
11
Transmission
Code
Comm. Parameter of POD
Memory TYPE Remarks
D
(data register/timer
•
counter/contact)
0
V (imer
•
counter/contact) 1
WS (system register) 2
WC (constant register) 3
X (input relay) 4
Y(output relay) 5
C(internal relay) 6
SC (special register) 7