Fujitronic UG520H-x Home Theater Screen User Manual


 
2 - 1
1 FUJI PLC 1
1
FUJI PLC • 1
(MICREX-F series)
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Switch Setting
MODE Switch: RS-232C: 1 RS-485: 3
RS-485 Port Setting SW: “0” for both x10, x1
RS-485 Terminal Resistor: ON
Character Switches
Port
Transmission
Control Mode
RS-232C
RS-422
0
19200bps
Even
7 (ASCII)
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Terminal Resistor at Receiver
Item Setting of PLC
0
19200bps
Even
7
1
Comm. Parameter of POD
Provided for RS-485
1 (Asynchronous non-protocol by command)(fixed)
3 (Asynchronous non-protocol by command)(fixed)
PLC
F70, F70S
NC1L-RS2
NC1L-RS4
FFU120B
FFK120A
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
Select PLC Type
MICREX-F
Series
F55 NV1L-RS2
RS-232C [Wiring Diagram 1]
F80H, F120H, F120S
F140S, F15xS
Wiring Diagram
Link Unit
8
No
7
6
ON
ON
ON
Setting Contents
Switch setting
Parity provided
Even
5
ON 7 bit
4
ON 1 bit
2
ON
3
1
ON
OFF
Same as POD
(normally 19200bps)