Result of the Test Cause Solution
Gauge reading increases and
decreases as % Open value is
changed and fluid flow does not
change or is not present.
The problem is mechanical:
restriction/plugged hose
plugged gun tip
fluid regulator failure
1. Clear any clogs.
2. Remove restrictions.
3. Clean and/or repair fluid regula-
tor.
Gauge reading does not increase
and decrease as % Open value is
changed.
The problem is electrical:
Fuse F2 is blown
disconnected wires or cables
pressure control failure
V/P valve failure
flow control board failure
1. Measure the voltage to the regu-
lator at one of two places:
At J5 on the fluid control
board, measure across the
white (pin 1) and black (pin 6)
wire connections. The volt-
age should be in the range of
0-3.3 Vdc for 0%-100% Open
command (approximately
1.65 Vdc for 50% Open).
At J2 on the flow control
board of the module, mea-
sure across the red (pin 1)
and black (pin 2) wire con-
nections. The voltage should
be in the range of 0-21 Vdc
for 0%-100% Open com-
mand (approximately 12 Vdc
for 50% Open).
2. If voltage is not present, check if
fuse F2 on the fluid control board
is blown.
3. If voltage is present, ensure the
cable is properly connected to
the module circuit board.
4. If cable is properly connected,
replace pressure control, VP
valve, and flow control board
sequentially to isolate failure. See
manual 3A2097.