6F8A0917
-
145
-
• Output example of one-shot pulse output
ON
OFF
0
100
200
Preset count set-point value: 100
Totalizer count
Preset output
Preset output OFF because
pulse width is reached.
Input/Output Timing Chart
* Preset output goes ON when the count value exceeds the preset value of 100 and the preset output
goes OFF when its width reaches the set pulse width.
When the preset value exceeds 100, the preset value is changed to 200 (adding the preset count of
100 to the current preset value of 100).
Then, the preset output goes ON when the count value exceeds the preset value of 200, and the
preset output goes OFF when its width reaches the set pulse width.
When the preset value exceeds 200, the preset value is changed to 300 (adding the preset count of
100 to the current preset value of 200).
Note: When the one-shot pulse output function is selected, if its pulse width is large compared
with the update interval of the preset value, the output stays ON. To make sure to output
a one-shot pulse, set the preset value so that
the conditions in the table below are
satisfied.
Pulse width setting
Preset count value condition
Interval that the preset value reaches
Example: Count rate: 0.01 l
Flow verosity: 10 l/s
Count-up rate:1ms/COUNT
50ms 100ms or more Preset count value: 100 or more
500ms 1000ms or more Preset count value: 1000 or more