4-76 Series 90-30/20/Micro Programmable Controllers Reference Manual – September 1998 GFK-0467K
4
Valid Memory Types:
Parameter flow %I %Q %M %T %S %G %R %AI %AQ const none
enable •
IN • • • • •† • • • •
ok • •
• Valid reference or place where power may flow through the function.
† %SA, %SB, %SC only; %S cannot be used.
Example:
In the following example, at power-up, 32 words of %Q memory (512 points) beginning at
%Q0001 are filled with zeros.
| _____
|FST_SCN | |
|——| |———| BLK_|—
| | |
| | CLR_|
| | WORD|
| | |
| %Q0001—|IN |
| | LEN |
| |00032|
| |_____|
|