4-96 Series 90-30/20/Micro Programmable Controllers Reference Manual – September 1998 GFK-0467K
4
Valid Memory Types:
Parameter flow %I %Q %M %T %S %G %R %AI %AQ const none
enable •
IN • • • • • • • • •
ok • •
Q • • • • • • • •
• Valid reference or place where power may flow through the function.
Example:
In the following example, whenever input %I0002 is set and no errors exist, the integer at input
location %I0017 through %I0032 is converted to four BCD digits, and the result is stored in
memory locations %Q0033 through %Q0048. Coil %Q1432 is used to check for successful
conversion.
| _____
|%I0002 | | %Q1432
|——| |———| INT_|———————————————————————————————————————————————————————————( )—
| | TO_ |
| | |
| | BCD4|
| %I0017—|IN Q|—%Q0033
| |_____|
|