When %Q or %M references are used with retentive coils, or are used as function block outputs,
the contents are retained through power loss and RUN-TO-STOP-TO-RUN transitions.
Retentive coils include retentive coils —(M)—, negated retentive coils —(/M)—, retentive SET
coils —(SM)—, and retentive RESET coils —(RM)—.
The last time a %Q or %M reference is programmed on a coil instruction determines whether the
%Q or %M reference is retentive or non-retentive based on the coil type. For example, if %Q0001
was last programmed as the reference of a retentive coil, the %Q0001 data will be retentive.
However, if %Q0001 was last programmed on a non-retentive coil, then the %Q0001 data will be
non-retentive.