Honeywell W7761A Universal Remote User Manual


 
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
11 74-2699
M6857
1
2
3
Fig. 5. DIN rail adapters.
The input/output points are summarized in Table 2.
Table 2. List Of Available Points.
W7761A
Digital Outputs 8 Triac Outputs
Digital Inputs 4
Analog Inputs 6
(4 Resistive and 2
Voltage/Current Inputs)
DC Power 20 Vdc available to
power optional sensors
(50 mA max.)
Floating (Series 60)
Control
Heating or Cooling
PWM Control Heating or Cooling
Performance Specifications
Power:
24 Vac with a minimum of 20 Vac and a maximum of 30 Vac at either 50 or 60 Hz. The W7761A power consumption is 6 VA
maximum at 50 or 60 Hz. The W7761A is a NEC Class 2 rated device. This listing imposes limits on the amount of power the
product can consume or directly control to a total of 100 VA (U.S. only).
The individual Triac outputs incorporate an internal common connection with the input power transformer. The Triacs provide a
switched path from the hot side (R) of the transformer through the load to the common of the transformer. The W7761A Device
design
must
use the same power transformer for any loads connected to that device; see Fig. 19.
Each individual Triac is rated 500mA at 30 Vac maximum. Under all operating conditions, the maximum load/source power
budget for the W7761A Device is 100 VA.