EXCEL 10 W7761A INPUT/OUTPUT DEVICE
57 74-2699
Table C3. Status Points (Left).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address NvName Field Name States plus Range State Default
AlarmNode nvoAlarm node 0 to 127 0
AlarmSubnet nvoAlarm subnet 1 to 255 0
AlarmType nvoAlarm type
0 to 255
NO_ALARM
INPUT_NV_FAILURE
NODE_DISABLED
SENSOR_FAILURE
rINPUT_NV_FAILURE
rNODE_DISABLED
rSENSOR_FAILURE
ALARM_NOTIFY_DISABLED
0
1
2
3
129
130
131
255
NO_ALARM
AlarmTypeLog0 nvoAlarmLog type0 Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.
NO_ALARM
AlarmTypeLog1 nvoAlarmLog type1 Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.
NO_ALARM
AlarmTypeLog2 nvoAlarmLog type2 Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.
NO_ALARM
AlarmTypeLog3 nvoAlarmLog type3 Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.
NO_ALARM
AlarmTypeLog4 nvoAlarmLog type4 Refer to the AlarmType
enumerated list shown in the
Eng. Units/States column.
NO_ALARM
Errorbyte1 nvoError error_bit(0)
Byte Offset = 0
Bit Offset = 0
ResSensor1Error(AI1)
FALSE
TRUE
0
1
FALSE
(continued)