EXCEL 10 W7761A INPUT/OUTPUT DEVICE
60 74-2699
Table C3. Status Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Calibrate (C), Monitor (M),
Parameter (P), Schematic (S)
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X M ResSensor2Error(AI2): Refer to the description of ResSensor1Error(AI1).
X M ResSensor3Error(AI3): Refer to the description of ResSensor1Error(AI1).
X M ResSensor4Error(AI4): Refer to the description of ResSensor1Error(AI1).
X Software version.
A four byte ASCII string indicating the type of node (model).
X Software version.
X Software version.
The NodeType is a numeric identifier that is stored in EPROM that identifies the
Excel 10 node type. Whenever a new software version or upgrade is issued, this is
reflected in nroPgmVer which typically is read by a network management node to
identify the node type. The contents of nroPgmVer contain compatible model type
information and is fixed at the time when the node software is compiled.
CommFailure:
This field is not supported and is set to 0 (FALSE).
disabled: disabled reports 1 if nvoIO mode is set to DISABLED_MODE or
FACTORY_TEST mode. Otherwise disabled is set to 0.
ElectricalFault:
This field is not supported and is set to 0 (FALSE).
FailSelfTest:
This field is not supported and is set to 0 (FALSE).
FeedbackFailure:
This field is not supported and is set to 0 (FALSE).
InAlarm: If there are currently any active alarms reported by InAlarm, or InAlarm is
set to AlarmNotifyDisabled, then InAlarm is set to True, if not InAlarm is set to False.
InvalidId: If object_id is not a valid object, invalid_id is set to 1 (TRUE) otherwise it is
set to 0 (FALSE).
InvalidRequest: If object_request is not a valid request for the object addressed,
InvalidRequest is set to 1 (TRUE) otherwise it is set to 0 (FALSE).
(continued)