Honeywell W7761A Universal Remote User Manual


 
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
79 74-2699
Voltage to A/D Sensor Voltage
0.00 0.00
0.50 0.25
1.00 0.50
1.50 0.75
2.00 1.00
2.50 1.25
3.00 1.50
3.50 1.75
4.00 2.00
4.50 2.25
5.00 2.50
5.50 2.75
6.00 3.00
6.50 3.25
7.00 3.50
7.50 3.75
8.00 4.00
8.50 4.25
9.00 4.50
9.50 4.75
10.00 5.00
0
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
1000 300 500 700 900200 400
600 800
1000
A/D VOLTS
VOLTS
SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D
M11612
Fig. E-10. Graph of Sensor Voltage versus input Voltage to A/D.
Sensor Type:
Third party.
Sensor Use:
Sensor Voltage (Vdc)/Pressure Inw (kPa) 2 to 10V, 0 to 5 inw (0 to 1.25 kPa).
Table E-11 lists the points for Sensor Voltage (Vdc) versus Pressure (Inw). Fig. E-11 shows the graph of these points.
Table E-11. Sensor Voltage (Vdc) Versus Pressure (Inw).
Pressure Inw (kPa) Sensor Voltage (Vdc)
0.00 (0.00) 2.00
0.50.(0.13) 2.80
1.00 (0.25) 3.60
1.50 (0.37) 4.40
2.00 (0.5) 5.20
2.50 (0.62) 6.00