EXCEL 10 W7761A INPUT/OUTPUT DEVICE
70 74-2699
Table C5. Direct Access And Special Points (Left).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address NvName Field Name States plus Range State Default
DestManMode nviManualMode MODE_ENABLE
MODE_DISABLE
MODE_MANUAL
SUPPRESS_ALARMS
UNSUPPRESS_ALARMS
0
1
2
3
4
MODE_ENABLE
Table C5. Direct Access And Special Points (Right).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Calibrate (C), Monitor (M),
Parameter (P), Schematic (S)
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X M P DestManMode: is an input which is used to manually set the physical outputs.
DestManMode remains unchanged until another mode has been commanded or an
application restart has been performed. The valid enumerated values are:
MODE_ENABLE enables the node so that the RIO controls the physical outputs as
the normal mode. MODE_ENABLE is the default state after power is restored or an
application restart occurs. If the mode was MANUAL and DestManMode is set to
MODE_ENABLE, the node then goes through application restart.
MODE_DISABLED sets the node into the DISABLED mode. The alarm
NODE_DISABLED is initiated, and the physical outputs are turned off. The physical
inputs, network variable inputs, and network variable outputs are still functioning
when the node is in the DISABLED mode.
MODE_MANUAL sets the node into the MANUAL mode. The alarm
NODE_DISABLED is initiated, and the physical outputs are controlled manually as
commanded by DestManMode. The nodes configuration variables and
DestManMode are used to set valves, dampers, and/or digital output to the desired
manual positions or state(s). The physical inputs, network variable inputs, and
network variable outputs are still functioning when the node is in the MANUAL mode.
SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED,
and AlarmTypeLog to no longer record alarms. If alarms are suppressed,
UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned to
reporting alarms. See nvoAlarm for more details. All unspecified values are the same
as MODE_ENABLE.