Honeywell W7761A Universal Remote User Manual


 
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
35 74-2699
Table 8. Excel 10 W7761A Device Ordering Information (Continued).
Part Number Product Description
Comments
Accessories (Continued):
ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series 60
ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60
EL7680A1008 Wall Mounted Wide View Infrared Occupancy Sensor
EL7628A1007 Ceiling Mounted Infrared Occupancy Sensor
EL7611A1003,
EL7612A1001
Ultrasonic Occupancy Sensors
EL7630A1003,
EL7621A1002,
EL7621A1010
Power Supply/Control Units for Occupancy sensors
C7400A1004 Solid State Enthalpy Sensor (4 to 20 mA) For outdoor and return air enthalpy
C7600B1000 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity
C7600C1008 Solid State Humidity Sensor (4 to 20 mA) For outdoor and return air humidity
C7600C1018 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity
MMC325-010,
MMC325-020
Pneumatic Retrofit Transducers.
Select pressure range: (010) 0 to 10 psi (68.97 kPa)
or (020) 0 to 20 psi (137.93 kPa).
Use to control Pneumatic reheat valves
MMCA530 DIN rail adapter for MMC325 Transducers
MMCA540 Metal enclosure for MMC325 Transducers
ML7984B3000 Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G Valves
ML6161B1000 Damper Actuator Series 60
M6410A Valve Actuator Series 60 Use with V5812/V5813 Valves
ML684A1025 Versadrive Valve Actuator with linkage, Series 60 Use with V5011 and V5013 Valves
ML6464A1009 Direct Coupled Actuator, 66 lb-in., Series 60
ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series 60
ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60
V5812A Two-way terminal unit water valve; 0.19, 0.29, 0.47,
0.74, 1.2, and 1.9 C
v
1/2 in. npt (13 mm) or
2.9 and 4.9 C
v
3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off
rating for 0.19 to 1.9 C
v
is 65 psi; for 2.9
and 4.9, C
v
is 45 psi. (Coefficient of
volume or capacity index C
v
=
g
allons per
minute divided by the square root of the
pressure drop across the valve.)
V5813A Three-way mixing terminal unit hot water valve; 0.19,
0.29, 0.47, 0.74, 1.2, and 1.9 C
v
1/2 in. npt (13 mm)
or 2.9 and 4.9 C
v
3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off
rating 0.19 to 0.74 C
v
is 55 psi; 1.2, and
1.9 C
v
is 22 psi; 2.9 and 4.9 C
v
is 26 psi.
R8242A Contactor, 24 Vac coil, DPDT
AT72D, AT88A, AK3310, etc. Transformers
EN 50 022 DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) Obtain locally: A controller requires 5 in.
Augat Inc. part number 2TK2D DIN rail (adapter) Purchase from Augat Inc. two DIN rail
adapters for each controller
Serial Interface Cable, male DB-9 to female DB-9 or
female DB-25.
Obtain locally from any computer
hardware vendor.
Cabling
Honeywell AK3791 (one
twisted pair) AK3792 (two
twisted pairs)
E-Bus (plenum): 22 AWG (0.34 mm
2
) twisted pair
solid conductor, nonshielded or Echelon
approved
cable.
Level IV 140°F (60°C) rating
Honeywell AK3781 (one
twisted pair) AK3782 (two
twisted pairs)
E-Bus (nonplenum): 22 AWG (0.34 mm
2
) twisted pair
solid conductor, nonshielded or Echelon
approved
cable.
Level IV 140°F (60°C) rating
Honeywell AK3725 Inputs: 18 AWG (1.0 mm
2
) five wire cable bundle Standard thermostat wire
(continued)