EXCEL 10 W7761A INPUT/OUTPUT DEVICE
54 74-2699
Table C1. Input/Output Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Calibrate (C), Monitor (M),
Parameter (P), Schematic (S)
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.
X X X M DI2State:
Refer to the description for DI1State.
SrcDigIn3Sts: Refer to the description for SrcDigIn1Sts above.
X X X M DI3State:
Refer to the description for DI1State.
SrcDigIn4Sts: Refer to the description for SrcDigIn1Sts above.
X X X M DI4State:
Refer to the description for DI1State.
X X X M SrcHumidAI5 is an output network variable corresponding to the voltage or current
input channel (AI5) if the selection for humidity sensor was made via ncirioIoSelect
for AI5.
X X X M SrcHumidAI6 is an output network variable corresponding to the voltage or current
input channel (AI6) if the selection for humidity sensor was made via ncirioIoSelect
for AI6.
X X X M SrcPressAI5 is an output network variable corresponding to the voltage or current
input channel (AI5) if the selection for a pressure sensor was made via
ncirioIoSelect for AI5.
X X X M SrcPressAI6 is an output network variable corresponding to the voltage or current
input channel (AI6) if the selection for a pressure sensor was made via
ncirioIoSelect for AI6.
X X X M SrcTempAI1 is an output network variable corresponding to the analog input
channel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1
applied to it.
X X X M SrcTempAI2 is an output network variable corresponding to the analog input
channel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2
applied to it.
X X X M SrcTempAI3 is an output network variable corresponding to the analog input
channel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3
applied to it.
X X X M SrcTempAI4 is an output network variable corresponding to the analog input
channel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4
applied to it.
X X X M SrcVoltageAI is an output network variable corresponding to the voltage or current
input channel (AI5 or AI6) if the selection for a voltage sensor was made via
ncirioIoSelect.