EXCEL 10 W7761A INPUT/OUTPUT DEVICE
45 74-2699
Table C1. Input/Output Points (Left).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address NvName Field Name States plus Range State Default
AI1RType ncirioIoSelect ResistiveIn0 DA_Temp_PT3000
OA_Temp_PT3000
RA_Temp_PT3000
Custom_PT3000
DA_Temp_20KNTC
RA_Temp_20KNTC
Space_Temp_T7770
Custom_20KNTC
Unused_Res_AI
0
1
2
3
4
5
6
7
255
Unused_Res_AI
AI2RType ncirioIoSelect ResistiveIn1 See AI1RType Eng. Units/States
column for selections
Unused_Res_AI
AI3RType ncirioIoSelect ResistiveIn2 See AI1RType Eng. Units/States
column for selections
Unused_Res_AI
AI4RType ncirioIoSelect ResistiveIn3 See AI1RType Eng. Units/States
column for selections
Unused_Res_AI
AI5VType ncirioIoSelect VoltageIn0 RA_Hum_C7600C
OA_Hum_C7600C
Filter_Diff_Pres
RA_Hum_C7600B
OA_Hum_C7600B
RA_Enthalpy
OA_Enthalpy
Space_CO2
Voltage_Monitor
Unused_Volt_AI
0
1
2
3
4
5
6
7
8
255
Unused_Volt_AI
AI6VType ncirioIoSelect VoltageIn1 See AI5VType Eng. Units/States
column for selections
Unused_Volt_AI
(continued)