GE GFK-0804B Universal Remote User Manual


 
4
4-33GFK-0804B Chapter 4 The Micro PLC Instruction Set
Examples and HHP Instructions
Ladder Diagram Hand-held Programmer
I1
START
MOVE
OUT
START
MOVE
OUT
F2
F1
F2
F1
I1
R1
5
R10
O9
8
O17
"
[R1E 5! R10]
N
L
[O9E 8! O17]
N
L
46139
In the first example rung above, when transitional contact I1 goes on, 5 registers (R1 –
R5) are copied to locations R10 – R14.
In the second rung, each program scan 128 bits (8 x 16) are copied from O9 – O137 to
locations O17 – O124. Since the locations being copied from overlap the locations being
copied into, this function actually has the effect of shifting 128 bits eight bits to the “left”