Mitsubishi Electronics AJ65bt-r2 Home Theater Server User Manual


 
10 - 4
MELSEC-
A
10 TROUBLESHOOTING
Error code
(hexadecimal)
Error name Cause of error Error remedy
BB93
Transmission data
size error
The transmission data size
exceeds the transmission
area size.
Correct the transmission data size designation area
(
R2
200H at default) and the transmission area size
(
R2
1H).
BB94
Error during
transmission
cancel request
signal ON
When the transmission was
requested, the transmission
cancel request signal
(RYn1) was already ON.
Request the transmission after turning the transmission
cancel request (RYn1) OFF.
BB95
User registration
frame
transmission error
The designated user
registration frame cannot be
transmitted.
Check that the designated user registration frame No.
has been registered.
BB96
Special character
usage error
A special character that
cannot be used for the head
frame during frame
transmission was
designated.
Correctly designate the transmission head frame No.
BB97
Table
transmission
information error
Data that cannot be
designated when
transmitting a transmission
table was designated.
Correct the data designated in the transmission table
(
R2
122H to 185H) and the monitor designation 1 to
64 (
R2
78H to F7H).
BB98
Registration frame
contents
transmission error
A special character that
cannot be transmitted was
used in the designated user
registration frame No.
Correct the contents of the registration data for the
designated user registration frame No.
BBA2
Reception data
size over error
The reception data exceeds
the maximum size of the
reception data.
Make sure that the reception data size fits in the value
designated with the reception area size designation
(
R2
3H).