Intel ZT 7102 TV Video Accessories User Manual


 
Intel
®
NetStructure
TM
ZT 7102 Chassis Management Module
Power Supplies
84 Technical Product Specification
13.5 Inhibiting Power Supplies
Power supplies can be inhibited through the CMM. This is accomplished using the following
command:
cmmset -l chassis -d psinhibitN -v 0
Where N is the number of the power supply that is to be inhibited.
Note: When a non-IPMI supply is inhibited, a SEL entry is logged indicating a failure condition. When
the non-IPMI supply is enabled a SEL entry is logged indicating that the power supply has
recovered from a failure condition. This does not occur in current IPMI-compliant power supplies.
13.6 Enabling Power Supplies
To enable a supply which has been inhibited, issue the following command:
cmmset -l chassis -d psinhibitN -v 1
Where N is the number of the power supply that is to be enabled.
Note: When a non-IPMI supply is enabled a SEL entry is logged indicating that the power supply has
recovered from a failure condition. This is because when a non-IPMI supply is inhibited, a SEL
entry is logged indicating a failure condition. This does not occur in current IPMI-compliant power
supplies.