LG Electronics 120S Universal Remote User Manual


 
Chapter 7 Usage of Various Functions
7-30
Relay response method.
PID parameters are obtained by On/Off operation during 1 cycle of PV variation.
PID parameters are obtained by amplitude and period of oscillation
The On/Off operation will be occur at the SV value.
Process reaction curve method(PRC method).
PID parameters are obtained by step response of process.
It is useful fo r time 1
st
order time delay system expressed as following
1+
Ts
e
K
Ls
Obtained parameters may not accurate if the process can’t approximated to 1
st
order system, In this
case, use relay response method.
SV
Period
Amplitude
MV
80% of SV

4000
Time delay(L)
63% of SV
Time constant(T)