LG Electronics 120S Universal Remote User Manual


 
Chapter 6 Input and Output Specification
6-11
6.3.3 Expansion Module
1) Specifications
Expansion Module
Model
Specifications
G7E-DR10A G7E-DR08A G7E-RY08A G7E-DR20A
Output point 4 points 8 points
Insulation method Relay insulation
Rated load Voltage/current
DC24V / 2A (Resistive load), AC220V / 2A (COS Ψ = 1) / 1 point 5A / 1COM
Min. load Voltage/current DC5V / 1mA
Max. load voltage/current AC250V, DC110V
Current leakage when off 0.1mA (AC220V, 60Hz)
Max. on/off frequency 1,200 times/hr
Surge Absorber None
Mechanical More than 20,000,000
Rated on/off voltage/current load 100,000 or more
AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 or more
AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 or more
Life
Electrical
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 or more
Off On
10 ms or lower
Response time
On Off
12 ms or lower
Operation indication LED is on at on status of output
2) Circuit
It’s the same with the output circuit of the main unit.
3)
Output wiring
DC5V
L
L L L
DC24V
AC110/220V
L
L
DC5V/24V