LG Electronics 120S Universal Remote User Manual


 
Chapter 7 Usage of Various Functions
7-36
c) operation parameters
Scan time : S_TIME=5 (sampling time = 0.5 seconds)
Auto / Manual operation setting : Auto
Output limit : Max. = 4000, Min = 0
High frequency noise removal ratio : 10
SV setting : 1300(60°C ),1350(70°C ),1400(80°C ),1500(100°C)
Current value setting : D4780(Digital value of RTD module Ch0)
BIAS setting : 0 (If only P control is used, input proper value other 0)
EN_P, EN_I, EN_D setting : input proper values
PWM setting : If enabled, input proper values.
SV Ramp setting : Input proper values.
Delta MV setting : Input proper values.
PID Algorithm setting : Select proper algorithm.
d) RTD module setting
Channel setting : use channel 0
RTD Type setting : Pt100
Digital conversion data registration area : D4780
e) D/A module setting
Channel setting : use channel 0
output range setting: DC 4 ~ 20 mA
D/A conversion data registration area : D4980
As a result of PID8AT execution, Proportional gain(P),Derivative time(D),
Inte
g
ral time
(
I
)
are stored D0102,D0103,D0104.