Chapter 7 Usage of Various Functions
7-38
6) Error code list
(1) PID8AT
Error Code
Description
Corrective action
H0100 Scan time setting range error Set scan time to available setting range
H0200 PV setting range error Set PV setting to available setting range
H0300 SV setting range error
Set SV to available setting range SV
If PRC identification method is selected, check current PV is
less than SV.(SV should be greater than PV)
(2) PID8
Error Code
Description
Corrective action
H0100 Scan time setting range error Set scan time to available setting range
H0200 Manual operation range error Setmanual opration value to available setting range
H0300 Output limit value error(Min.)
Set minimum output limit value to available setting range and
Set it less than maximum output limit value
H0400 Output limit value error(Max.)
Set maximum output limit value to available setting range and
Set it greater than minimum output limit value
H0500 High frequency noise removal ratio setting error Set this parameter to available setting range
H0600 Mode command set error
Available mode command set are P, PI, PID(PWM for each),
On-Off only.
H0700 PWM period setting error Set PWM period to available setting range
H0800 P gain setting error Set P gain period to available setting range
H0900 I time setting error Set I time period to available setting range
H0A00 D time setting error Set D time period to available setting range
H0B00 Bias setting error Set Bias to available setting range
H0C00
PV setting range error
Set PV to available setting range
H0D00 SV setting range error Set SV to available setting range
H0E00 SV Ramp setting error Set SV Ramp to available setting range
H0F00 Delta MV setting error Set Delta MV to available setting range
H1000 PID algorithm setting error Check PID algorithm setting
H1100 Operation mode setting error Available operation mode is 0 or 1