122
(3) Switch setting
Open the "I/O assignment" tab.
Parameter [PLC parameter] [I/O assignment] button
In counting speed setting, "500kPPS" can be selected for the LD62 only. Do not set "500kPPS" for the LD62. Doing so
will result in incorrect count.
Switches 3 to 5 fields in "Switch setting for I/O and intelligent function module" are used by the system and are not
available for users. Always leave these fields blank. If a value is set, the performance of the high-speed counter module
is not guaranteed.
Item Setting item Description
Switch 1 (for CH1)
Pulse input mode
0: 1-phase multiple of 1
1: 1-phase multiple of 2
2: CW/CCW
3: 2-phase multiple of 1
4: 2-phase multiple of 2
5: 2-phase multiple of 4
Select a pulse input mode.
Counting speed setting
0: 10kPPS
1: 100kPPS
2: 200kPPS
3: 500kPPS (LD62D only)
Select a counting speed.
Counter type
0: Linear counter
1: Ring counter
Select a counter type.
Switch 2 (for CH2) The setting items are the same as those for Switch 1 (for CH1).
Switch 3
Blank
Leave the fields blank if values have been set.
Switch 4
Switch 5
Select "HEX.".
0
H