Mitsubishi Electronics 0 Universal Remote User Manual


 
71
CHAPTER 8 FUNCTIONS
8
8.3 Coincidence Output Function
(b) Setting interrupt pointers
Assign interrupt factors (SI) and the interrupt pointers of the CPU module in "Intelligent Function Module
Interrupt Pointer Setting" of "PLC Parameter".
Project window [Parameter] [PLC Parameter] [PLC System]
[Intelligent Function Module Setting] button
Assigning SI0 to SI3 of the high-speed counter module, whose start I/O number has been set to 20, to the
interrupt pointers I50 to I53
Item Description Setting range
PLC Side
Interrupt Pointer Start No.
Enter the start number of the interrupt pointer of the
CPU module.
50 to 255
Interrupt Pointer Count Enter the number of interrupt factors (SI). 1 to 4
Intelligent Module Side
Start I/O No.
Enter the start I/O number of the high-speed counter
module.
0000
H
to 0FF0
H
Start SI No.
Enter the start number of the interrupt factor (SI) of
the high-speed counter module.
0 to 3
Ex.