6.5 Examples of Wiring with External Output Terminals
To use the coincidence output terminal (EQU), an external power supply of 10.2 to 30VDC is required to drive the
internal photocoupler. The following figure shows the wiring example:
(1) For the high-speed counter module (sink output type)
*1 Install a fuse for each external terminal to prevent the external devices or module from being burnt out or damaged if a
load shorts in an output circuit.
Load
Load
A06(A05)
B06(B05)
A02, A01
B02, B01
EQU1
EQU2
0V
12/24V
10.2 to
30VDC
Fuse*
1
Fuse*
1
LD62, LD62D
In parentheses, terminal numbers of channel 2 are shown.