Mitsubishi Electronics QJ72LP25-25 Universal Remote User Manual


 
3 - 47 3 - 47
MELSEC-Q
3 SPECIFICATIONS
[W input transmission delay time (T
DB1)] (END asynchronization)
[Remote master station scan time (Sm) > link scan time (LS)]
T
DB1 = Sm + m + Sm + TRBF [ms]
TRBF
T
DB1
MOV W0 D0
0E
Sm
m
0E
Sm
m
0E
Sm
m
0E
Sm
m
0E
Sm
m
0E
Sm
LS LS LS LS LS LS LS
0: 0 step
E: END step
Buffer memory
Intelligent function
module
Remote master station
Link scan time
Remote I/O station
[Remote master station scan time (Sm) < link scan time (LS)]
T
DB1 = LS 2 + Sm + m + Sm + TRBF [ms]
TRBF
T
DB1
MOV W0 D0
0E
Sm
m
0E
Sm
m
0E
Sm
m
0E
Sm
m
0E
Sm
m
0E
Sm
LS LS LS
0: 0 step
E: END step
Buffer memory
Intelligent function
module
Remote master station
Link scan time
Remote I/O station
Sm
m
LS
T
RBF
: Remote master station scan time
: Remote master station link refresh time
: Link scan time
: Intelligent function module buffer memory refresh time
POINT
When the "Block send/receive data assurance per station" box is checked, the
transmission delay time (T
DB1) is calculated as follows:
Remote master station scan time (Sm) > Link scan time
T
DB1 = (Sm + m) 2 + Sm + TRBF + LS [ms]
Remote master station scan time (Sm) < Link scan time
T
DB1 = LS 3 + Sm + m + Sm + TRBF [ms]