Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
Page 106 Modbus Parameters 51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Alarm 5 Type 6208 0x1840 R/W
Value
Alarm 5 Type
0 Process High Alarm
1 Process Low Alarm
2 Deviation Alarm (SP-PV)
3 Band Alarm
4 Loop Alarm
5 Input/Sensor Break Alarm
6 Auxiliary Input A Break Alarm
7 Auxiliary Input B Break Alarm
Alarm 5 Value 6209 0x1841 R/W Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 5 Hysteresis 6210 0x1842 R/W Limited by the input span
Alarm 5 Inhibit
Enable/disable
6211 0x1843 R/W
Value
Alarm 5 Inhibit Enable
0 Disabled
1 Enabled
Alarm 5 Status 6212 0x1844 RO
Value
Alarm 5 Status
0 Inactive
1 Active
Alarm 5 Inhibit
Status
6213 0x1845 RO
Value
Alarm 5 Inhibit Status
0 Not Inhibited
1 Inhibited
Recorder & Clock Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Recording Sample
Interval
7550 0x1D7E R/W
Value
Recording Sample Interval
0 Every Second
1 Every 2 Seconds
2 Every 5 Seconds
3 Every 10 Seconds
4 Every 15 Seconds
5 Every 30 Seconds
6 Every Minute
7 Every 2 Minutes
8 Every 5 Minutes
9 Every 10 Minutes
10 Every 15 Minutes
11 Every 30 Minutes
Recording Mode 7551 0x1D7F R/W
Value
Recording Mode
0 Record until memory used
1 Continuous FIFO buffer
Start Stop
Recording
7552 0x1D80 R/W
Value
Operator Start
/Stop Recording
0 Stop Recording