DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009 Specifications Page 177
Output Specifications
Output Module Types
Option Slot 1 Options:
Single Relay, Single SSR Driver, Triac or DC linear.
Option Slot 2 Options:
Single Relay, Dual Relay, Single SSR Driver, Dual SSR Driver, Triac,
DC Linear or 24VDC Transmitter Power Supply.
Option Slot 3 Options:
Single Relay, Dual Relay, Single SSR Driver, Dual SSR Driver, Triac,
DC Linear or 24VDC Transmitter Power Supply.
Option Slot 4 Options:
Quad Relay.
Single Relay Output Performance
Contact Type:
Single pole double throw (SPDT).
Contact Rating:
2A resistive at 240V AC
Lifetime:
>500,000 operations at rated voltage/current.
Isolation:
Reinforced safety isolation from inputs and other outputs.
Dual Relay Output Performance
Contact Type:
2 x Single pole single throw (SPST) with shared common.
Contact Rating:
2A resistive at 240V AC.
Lifetime:
>200,000 operations at rated voltage/current.
Isolation:
Reinforced safety isolation from inputs and other outputs.
Quad Relay Output Performance
Contact Type:
4 x Single pole single throw (SPST).
Contact Rating:
2A resistive at 240V AC.
Lifetime:
>500,000 operations at rated voltage/current.
Isolation:
Reinforced safety isolation from inputs and other outputs.
Single Dual SSR Driver Output Performance
Drive Capability:
10VDC minimum at up to 20mA load.
Isolation: Not isolated from the universal input, Ethernet communications or
other SSR driver outputs.
Dual SSR Driver Output Performance
Drive Capability:
10VDC minimum at up to 20mA load.
Isolation: Not isolated from the universal input, Ethernet communications or
other SSR driver outputs.