Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
Page 96 Modbus Parameters 51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
14 Event 1 AND Alarm 1. Direct Acting
15 Event 1 AND Alarm 1. Reverse Acting
16 Event 2 AND Alarm 2. Direct Acting
17 Event 2 AND Alarm 2. Reverse Acting
18 Event 3 AND Alarm 3. Direct Acting
19 Event 3 AND Alarm 3. Reverse Acting
20 Event 4 AND Alarm 4. Direct Acting
21 Event 4 AND Alarm 4. Reverse Acting
22 Event 5 AND Alarm 5. Direct Acting
23 Event 5 AND Alarm 5. Reverse Acting
Output 3 Retransmit
Minimum
2211 0x08A3 R/W Limited by input range maximum/minimum
Output 3 Retransmit
Maximum
2212 0x08A4 R/W Limited by input range maximum/minimum
Option Slot 4 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 4
Module Type
2222 0x08AE RO
Value
Module Fitted In Slot 4
0 None Fitted
1 Quad Relay
255
Error (
unrecognised module
)
Digital Output 4
Status
2223 0x08AF RO
Value
Digital Output 4A, 4B, 4C & 4D Status
0 All outputs inactive
Bit 0 Output 4A Active
Bit 1 Output 4B Active
Bit 2 Output 4C Active
Bit 3 Output 4D Active
Digital Output 4A
Function
2230 0x08B6 R/W
Value
Digital Output 4A Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
4 Alarm and Event
Digital Output 4B
Function
2231 0x08B7 R/W
Value
Digital Output 4B Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
4 Alarm and Event