Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009 Modbus Parameters Page 129
Instrument Data
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Serial Number 1 210 0x00D2 RO The first 4 digits of the instrument’s Serial number.
Serial Number 2 211 0x00D3 RO The digits 5 to 8 of the instrument’s Serial number.
Serial Number 3 212 0x00D4 RO The digits 9 to 11 of the instrument’s Serial number.
Serial Number 4 213 0x00D5 RO The digits 12 to 14 of the instrument’s Serial number.
Manufacture Day 370 0x0172 RO Date of manufacture – 1 to 31 (day of month)
Manufacture Month 371 0x0173 RO Month of manufacture – 1 to 12
Manufacture Year 372 0x0174 RO 4 digit number = Year of manufacture (e.g. 2008)
USB Option Fitted 7503 0x1D4F RO
Value
USB Option
0 Not Fitted
1 Fitted
Data Recorder
Fitted
7868 0x1EBC RO
Value
Data Recorder Fitted
0 Not Fitted
1 Fitted
Profiler Enabled 8199 0x2007 RO
Value
Profiler Enabled
0 Profiler Not Enabled
1 Profiler Enabled
Software PRL 208 0x00D0 RO Product Revision Level – Firmware Level
Hardware PRL 207 0x00CF RO Product Revision Level – Hardware Level
Firmware Type 217 0x00D9 RO Firmware major version number
Firmware Version 218 0x00DA RO Firmware minor version number
Contact Details 1 400 0x0190 R/W 7 lines of user definable text - 25 ASCII characters
per line which can re read or written using Modbus
functions 16 or 23. Valid characters are 0 to 9, a to z,
A to Z, plus ( ) - and _.
Example. To write “My Company Name” to line 1
send:
[ADDRESS], 16, 01, 90, 00, 08, 10, 4D, 79, 20, 43,
6F, 6D, 70, 61, 6E, 79, 20, 4E, 61, 6D, 65, [CRC]
Contact Details 2 401 0x0191 R/W
Contact Details 3 402 0x0192 R/W
Contact Details 4 403 0x0193 R/W
Contact Details 5 404 0x0194 R/W
Contact Details 6 405 0x0195 R/W
Contact Details 7 406 0x0196 R/W