DCP200 Profile Controller & Recorder - Product Manual
Page 112 Modbus Parameters 51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
10 Every 15 Minutes
11 Every 30 Minutes
Values To Display In
Trend View
9001 0x2329 R/W
Value
Trend View Data
0 None (trend view off)
1 Process variable only
2 Process variable and setpoint
3 Process variable maximum & minimum
since last sample
Profiler Control & Status Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Profile Run/Hold
Signal
8192 0x2000 R/W
Value
Profile Run/Hold Sig
nal Source
0 Operator Key Press Only
1 Digital input A
2 Digital input B
Profile Abort Signal 8193 0x2001 R/W
Value
Profile Abort Signal Source
0 Operator Key Press Only
1 Digital input A
2 Digital input B
Active Profiler
Number
8243 0x2033 R/W Currently selected profile number (1 to 64)
Active Segment
Number
8244 0x2034 RO Currently active segment (1 to 255)
Profiler Control
Commands
8245 0x2035 R/W
Value
Profiler Command
0 Do nothing
1 Run the currently selected profile
2 Hold the currently running profile
3 Abort the currently running profile
4 Jump to the next segment
5 Release the hold
6 Exit profiler, return to controller mode
Note:
The Profiler Control Commands
must
be followed by a
Profiler Control Confirmation Action command.
Profiler Control
Confirmation Action
8257 0x2041 R/W
Value
Implement Profiler Command
0 Do Not Implement Command
1 Implement previous Profiler Command
Enable Edit While
Running
8262 0x2046 R/W
Valu
e
Editing Current Running Profile
0 Editing current running profile forbidden
1 Editing current running profile allowed
Profile Control In
Operation Mode
8260 0x2044 R/W
Value
Profile Control From Operation Mode
0 Operation Mode profile control disabled
1 Operation Mode profile control enabled
Profile Cycles Run 8247 0x2037 RO The Number of times the currently running profile has
cycled